Bouygues Energies

Air quality monitoring

Project

Renovation of a listed building in the center of Paris to house an art collection and the offices of a VIP.

}

Duration : 1 month

Challenge

The end customer was bothered by a persistent odor in one of the newly renovated offices and could not determine the origin or cause.

A

Need: monitor air quality and odors

Com’in solutions

A POD sensor was installed in the office in question and after a one-week training period, we were able to detect the odor variation.

The generated readings allowed us to visualize in time the evolution of this odor variation associated with a formaldehyde peak in the air and to correlate it to the activation of the ventilation.

We could trace the fact that the ventilation ducts had been cleaned with a product containing this chemical compound.

Need more information ? Send us a message.

Whether you have a question about our solutions or just want to talk, don't hesitate to contact our team by phone:

Call us